Manual 2100-450L
Page 7 of 14
17
12
FULLY OPEN150020
16145019
15140018
14135017
12130016
11125015
10120014
9115013
81100
MIS-3009 A
4-20mA AN (ppm) Damper (1)
Approc. Blade
Position (2)
4 700 FULLY CLOSED 0
5 750 1
6 800 2
7 850 3
8 900 4
9 950 5
10 1000 6
11 1050 7
Settings Recommended Default
RON Not Used
ROF Not Used
DSP C CT
UNI US US
COL 700 0
COH 1500 2000
TOL Not Used
TOH Not Used
BAR
See Instrution with Controller
For High Altitude Installations
CAL Used for Field Calibration
(1) Damper should be fully closed at 700 ppm, if not Potentiometer R7 can be adjusted
clockwise (CW) to close it. If it is fully closed at 700 ppm or lower no adjustments required.
(2) Blade as referenced to the Blade Position Label.
PRESS UP AND DOWN
ARROWS TO ENTER
CONFIGURATION MODE
USE ARROWS TO SELECT
SETTING. PUSH MIDDLE
BUTTON TO CHANGE.
CONTROLLER WILL
SHOW SET.
FOR PROPER OPERATION
POSITIONED AS SHOWN
JUMPERS MUST BE
NOTE: MENU
JUMPER MUST
BE SET TO "ON"
TO CHANGE ANY
SETTINGS WITH
THE FRONT BUTTONS.
TO LOCK THE CO2
CONTROLLER MOVE
JUMPER TO "OFF" AFTER
IT HAS BEEN CONFIGURED
FIGURES 3 & 4
CO
2
SENSOR DEFAULT & FINAL SETTINGS
8403-067 CO2 CONTROLLER